|
Headroom in a SPD
What It Is and What It Means To You
By Glenn Clifford
Senior Electrical Engineer
MCG Surge Protection, Deer Park, NY
(800) 851-1508
August 9, 2011
Ever
since the IEEE Std. 587 was released back in 1980, “low clamp
voltages” have been keywords in the surge protection industry.
Surge Protection Devices (SPD) are marketed to point to this very
low clamp voltage in the hope that customers will assume that these
must be the best solution to protect their valuable equipment and
data. Problem thus becomes, what affect does this close clamp
voltage have on the life of an SPD and how practical is a low clamp
voltage if it dramatically decreases protector life?
Ideally, a surge protector is purchased, installed and forgotten
about. It should work quietly and effectively for 20+ years without
a problem. During its lifetime, the SPD should be clamping
transients to a safe level, while causing no harm to equipment or
data. Designing a protector with a clamp voltage too close to the
utility voltage is one way to prevent damage, but it’s
short-sighted. In actuality, designing a protector in this manner
makes for a good data sheet but ultimately the product is going to
be particularly vulnerable to damage and a shortened lifespan.
Sensitive equipment is now left hanging along the line, laid bare to
any and all over voltages that course through AC and data lines
everyday.
By
typical industry standards, utility power is allowed to be plus or
minus 10% of nominal for extended periods of time. Utility
companies (in developed nations) follow this and generally hold to
it. However, there are circumstances that are out of the control of
the utility companies that can trigger unforeseen variations in
power. Sometimes for short periods, seconds to minutes, it is
possible to see normal fluctuations in the order of 15 to 20%.
These can result from a variety of occurrences such as everyday
utility switching, large inductive loads instantly either going on
or off line like elevators and even traffic accidents involving
power poles.
Surge
protection companies design various protectors utilizing several
different technologies. By and far the most reliable protectors use
MOV technology for AC power applications. An MOV is a metal oxide
varistor which is used in shunt to divert transients away from
sensitive electronics. Under normal conditions an MOV appears to
the circuit as a high impedance connection until the voltage
threshold is reached. At that point the MOV becomes a short circuit
“clamping” the over voltage down to a safe level. When the voltage
returns below the threshold level, the MOV reverts automatically to
a high impedance connection.
For
transients, high voltage anomalies lasting generally less than
500us, the MOV operates over and over again with very little
degradation as long as the current level is below what the MOV can
handle or there are enough MOV sharing the transient that the
current remains below what each MOV can withstand. MOVs offer
clamping characteristics close to an ideal clamping device
(Littelfuse AN9768 January 1998 Transient Suppression Devices and
Principles p. 10-106) while still offering high-energy
capability along with a relatively low price. There are many
different clamping devices available but none measure up to the
ability of the MOV to clamp high energy transients commonly observed
on power lines.
The
problem where many surge protectors become damaged is either when a
protector is undersized or more often, when the MOV finds itself
clamping longer duration surges. This is where headroom now becomes
critical.
Headroom can be
explained as the difference in voltage between the peak of the sine
wave and a higher voltage level where the MOV starts to turn on. If
the difference between the two is too small, the MOV may conduct
more frequently, resulting in a shorter MOV life. Headroom margins
of 15% and greater address this issue with virtually no effect on
suppressor performance. In some areas, power line fluctuations can
exceed 15%. A good SPD design requires higher clamp voltage MOV in
these situations.
It is
not only 120V systems that are at risk; systems such as 277/480Y are
also at risk of fluctuation. Recently MCG encountered a problem
with a unit installed on a 277/480V line. The building was under
construction and the power was being taken on and off line
periodically. This caused voltage swings most likely in the order
of several cycles. Standard SPDs were being damaged. An MCG
protector utilizing high headroom MOVs rode through it all,
continuing to protect equipment from the real hazards of high
amplitude transients.
A
standard MOV has a tolerance of +/-10%. That translates to a MOV
with a published MCOV of 320V could come in as high as 352V at +10%
or as low as 288V at -10%. Assuming we have a MOV with -5%, which
is not unreasonable, that gives an MCOV of 304V a headroom of only
27V.
Here
are some possible power fluctuations:
277V + 10% = 304.7V
277V + 15% = 318.5V
277V + 20% = 332.4V
With
this data it is easy to see that a 320V MOV with -5% or 304V will be
too close for comfort on the 277V + 10% but will probably survive
without any incident, even for long periods of time. The outlook for
the 277V + 15% is not so favorable. Although this may be less
common in countries or areas with well-regulated power, there are
circumstances where it will occur. This MOV will fail if the voltage
remains constant longer than just a few minutes. It will definitely
begin to degrade if it is just clamping each peak of the sine wave
for a short time. Finally, the 277V + 20% is going to cause the MOV
to overheat and degrade significantly or just fail outright even in
as short an amount of time as 1/2s. Although this is not a very
likely scenario, it can and does happen from time to time with
devastating effects to any surge protective device that is trying to
impress with low clamping results on its data sheet.
Higher headroom does not present a problem to equipment. The
Information Technology Industry Council (ITI) publishes a curve that
shows the susceptibility of typical business equipment. In the
industry it is known as the ITI (CBEMA) Curve. (Information
Technology Industry Council (ITI) ITI (CBEMA) Curve Application
Note (http://www.itic.org/clientuploads/Oct2000Curve.pdf))
This
curve was made for single phase 120V equipment, the most vulnerable
to transients, but can be extrapolated for any voltage. Refer to
Figure 1. This curve clearly shows that equipment can withstand
higher transient voltages for very short durations.
A
higher headroom approach, for example, uses a 390V MOV on 277V
systems. In a “worst case” intendment, an MOV at -10% is applied.
That equals 351V, still well above the 332.4V that can be seen with
utility +20%.
In
conclusion, when protectors are designed to clamp too close to the
utility power, the outlook for downstream equipment is poor. The
protector becomes damaged prematurely and oftentimes, leaves the
facility and equipment unprotected until the protector is repaired
or replaced. Using higher headroom MOV does give a slightly higher
clamp voltage but it is still well within guidelines to protect
equipment for short durations of transients, typically much less
than 500us.
Along
with this common-sense design innovation, adding a low inductance
cable can lower the voltage drop up to 1/3 of standard wiring.
Using multiple Neutral wires alongside the phase wires and twisting
the wires tightly along the run is one way to accomplish this. This
two-prong approach offers excellent surge protection performance.
Adding a 20-year product warranty and lifetime on protection modules
further ensures maximum equipment uptime.
###end##
Glenn
Clifford is a Senior Electrical Engineer at MCG Surge Protection.
The company has exclusively been in the surge protection business
for over 40 years.
Figure 1 – or refer to page three of the
attachment
http://www.itic.org/clientuploads/Oct2000Curve.pdf |